Three recessed lights, separate mirror task light, and concealed LED at the vanity. Device positions are a concept for the electrician.

Second-floor bathroom electrical concept, E-02 The existing A-02 geometry appears in pale grey. Three recessed lights, one vanity task fixture, concealed LED behind the mirror and below the vanity, one exhaust fan, four light dimmers, and one fan timer. G1 serves the vanity. G2 serves the separate proposed Brondell L60-EW heated seat. Both GFCI receptacles form part of the base scope. The electrician must approve the heated-seat cord reach, load, outlet height, location, circuit and protection. J1 marks an unresolved towel warmer connection near the tub. The filler stays left of the tub. The towel warmer stays on the east wall at the tub centreline. Dashed curves show control associations, not cable routes. All electrical locations require a Licensed Electrical Contractor's approval. One SVG unit equals one inch. Print at 1:24 on landscape letter paper at actual size. 7' 10 3/4" / 94 3/4" 7' 11 1/4" / 95 1/4" Existing window Freestanding tub Toilet Vanity Entry Warmer 4 D + 1 T L1 L2 L3 EF1 V1 BL1 UL1 G1 G2 J1HOLD CB1 E-02 / Electrical concept Devices / 3000 K light L1 / Tub LED, wet-rated L2 + L3 / General LED V1 / Mirror task fixture BL1 / Behind mirror UL1 / Below vanity EF1 / Ceiling exhaust fan G1 / Vanity GFCI G2 / Heated-seat GFCI J1 / Warmer supply HOLD CB1 / Entry control bank D1: Tub / D2: General D3: Task / D4: Concealed LED T1: Fan timer, not a dimmer Dashed curves = control groups. They do not show cable routes. Contractor approval required J1: No approved rough-in point. Confirm wet-zone / product rules. Ceiling: 8' assumed; verify on site. Second-floor bathroom Reflected ceiling / electrical concept. Not for construction. 01'2' 1/2" = 1'-0" / 1:24Print at 100% / Letter

Contractor review

The towel warmer remains aligned with the tub. J1 marks an unresolved electrical connection, not an approved rough-in point. The electrician must approve the ICO K4025W supply, control access, and wet-zone clearances before work.

The plan includes two GFCI receptacles. G1 serves the hair dryer and general vanity use. G2 serves the separate proposed Brondell L60-EW heated seat. Both form part of the base scope.

Brondell lists 120 V, 60 Hz, 55 W maximum and a 48-inch cord. Its manual requires a grounded GFCI outlet. The electrician must approve the outlet height, cord route, circuit and protection. Heated-seat specifications.

The regular toilet needs no power. The proposed white toilet and seat require colour and physical fit approval before purchase.

Four dimmers separate the tub, general, task, and concealed light. T1 controls the fan. The installer must confirm each load and control combination.

Ceiling height is an 8-foot assumption. The ceiling points require a joist survey, duct route, and light-level check. Heights above the floor remain unset.

ESA identifies GFCI protection near water and product-specific rules for heated bathroom devices. Enclosed receptacles need a separate interlock review. ESA guidance.

The proposed DALS family supports wet locations and 3000 K. The supplied version and compatible dimmer remain purchase checks. Manufacturer details.

The ICO manual requires GFCI-protected power and a bottom-right box. Its built-in switch and tub separation require approval. Warmer manual.

Device locations

Coordinates use inches from the inside northwest corner. The x-axis points east. The y-axis points south. Symbols do not set device size.

TagDevicex, y (in)ControlStatus
L1Recessed LED above tub; wet-location approved assembly38.25, 20.75D1Proposed
L2General recessed LED near the entry30, 69D2Proposed
L3General recessed LED in front of the vanity73, 54D2Proposed
EF1Panasonic FV-0511VQ1 ceiling fan, white grille; duct and airflow by contractor48, 45T1Proposed; fan timer and site fit require approval
V1One Kuzco Nola VL57718-BK/GO task fixture above the mirror, with three compatible 3000 K dimmable lamps70.75, 95.25D3Proposed; lamp, dimmer, height and mirror-door clearance require approval
BL1Concealed LED behind the mirror cabinet; accessible driver outside the cabinet storage volume70.75, 93.25D4Approved assembly and driver selection pending
UL1Concealed LED below the floating vanity; accessible driver and splash-rated assembly70.75, 76.75D4Approved assembly and driver selection pending
G1GFCI receptacle above the counter on the east wall for a hair dryer and personal care94.75, 85NoneProposed; electrician sets height and circuit
G2GFCI receptacle for the separate Brondell L60-EW heated-only toilet seat, 55 W maximum0, 67NoneRetained provision for the proposed seat; colour, physical fit, cord route, height, circuit and protection require approval
J1ICO K4025W warmer coordination marker only; its actual bottom-right connection location is not approved94.75, 20.75NoneHOLD: nameplate, GFCI supply, wet-zone clearance and control reach require electrician approval
CB1Four light dimmers and one fan timer on the existing angled wall beside the entry7.75, 83.75NoneProposed; wall depth, device width, height and door clearance require site confirmation