Ensuite bathroom proposed electrical plan, sheet E-01 Electrical locations over the A-01 floor plan. Interior room size: 112 by 124.875 inches. Four 6-inch recessed lights and two task lights above the basin centres. M1 and M2 are two framed wall mirrors, each 24 inches wide by 32 inches high, centred at y79.875 and y109.875 inches. Confirm their height and clearances from the task lights and GFCI outlets. BL1 and BL2 are two concealed LED runs, one around the frame of each mirror. They share ambient dimmer D4 with one niche LED, NL1. NL1 sits at the top of N1, 66 inches above the finished shower floor, and directs 3000K light downward. Its complete assembly requires wet-location approval and an accessible driver outside the shower. Two exhaust fans, one at the room centre and one above the toilet, three GFCI receptacles, a five-control bank G1 serves the vanity, G2 serves the hair dryer, and G3 serves the heated seat. B1 identifies the handheld bidet beside the toilet. The single existing window remains on the toilet wall. Dashed lines indicate control groups, not cable routes. A Licensed Electrical Contractor must finalize the electrical design before work. One drawing unit equals one inch; print at 1:32. M1 M2 Open 112" 28"56"28" 124 7/8" Bench Floating* Shower / 112" x 48" Low curb DL1 4" gap HH1 Handheld Shower 01 Fixed + HH1 HH2 Handheld Shower 02 Fixed + HH2 Entry Toilet N1 B1 Vanity Existing window L1 L2 L3 L4 EF1 EF2 BL1 BL2 NL1 V1 V2 G1 G2 G3 SS SS S CB1 D1 / D2 D3 / D4 F1 Electrical symbols L1-L4 Recessed 6" LED / 4 total L1-L2: wet-location listed for the shower. V1-V2 Nola task lights / 2 total BL1-BL2 Mirror surround / 2 total NL1 Niche-top LED / 1 total / 3000K 66" above shower floor; light downward. Complete wet-location assembly required. EF1-EF2 Ceiling exhaust fans / 2 total Duct each fan outdoors. EF2 sits over the toilet. G1 Vanity GFCI / above counter G2 Hair dryer GFCI / above counter G3 Heated seat GFCI / confirm height M1, M2: 24" x 32" each / GFCI fit TBD. CB1 / Entry control bank D1L1 + L2Shower dimmer D2L3 + L4General dimmer D3V1 + V2Vanity dimmer D4BL1 + BL2 + NL1Ambient dimmer F1EF1 + EF2Fan switch Proposed centre locations DeviceX / from leftY / from top L1 / L228" / 84"24" L3 / L428" / 84"84" V1 / V2112"79 7/8" / 109 7/8" BL1 / BL2112"79 7/8" / 109 7/8" NL156"-1 1/2" EF1 / EF256" / 18"60" / 109" G1 / G2112"90" / 120" G331"124 7/8" CB10"92" 01'2' Actual size / 100% * Bench support and drain cover removal / cleaning access: confirm before work. Dashed lines: control groups, not cable routes. NL1 driver: accessible outside shower. Electrician: approve complete LED assembly, dimmer and protection. Ensuite bathroom Proposed electrical / reflected ceiling plan SheetE-01 Scale at letter size 3/8" = 1'-0" / 1:32 Date05 Sep 2026 Preliminary / not for construction Licensed Electrical Contractor review required