Ensuite
Second floor
A-01 Floor plan
E-01 Electrical
Materials
Ensuite bathroom proposed electrical plan, sheet E-01
Electrical locations over the A-01 floor plan. Interior room size: 112 by 124.875 inches. Four 6-inch recessed lights and two task lights above the basin centres. M1 and M2 are two framed wall mirrors, each 24 inches wide by 32 inches high, centred at y79.875 and y109.875 inches. Confirm their height and clearances from the task lights and GFCI outlets. BL1 and BL2 are two concealed LED runs, one around the frame of each mirror. They share ambient dimmer D4 with one niche LED, NL1. NL1 sits at the top of N1, 66 inches above the finished shower floor, and directs 3000K light downward. Its complete assembly requires wet-location approval and an accessible driver outside the shower. Two exhaust fans, one at the room centre and one above the toilet, three GFCI receptacles, a five-control bank G1 serves the vanity, G2 serves the hair dryer, and G3 serves the heated seat. B1 identifies the handheld bidet beside the toilet. The single existing window remains on the toilet wall. Dashed lines indicate control groups, not cable routes. A Licensed Electrical Contractor must finalize the electrical design before work. One drawing unit equals one inch; print at 1:32.
M1
M2
Open
112"
28"
56"
28"
124 7/8"
Bench
Floating*
Shower / 112" x 48"
Low curb
DL1
4" gap
HH1
Handheld
Shower 01
Fixed + HH1
HH2
Handheld
Shower 02
Fixed + HH2
Entry
Toilet
N1
B1
Vanity
Existing window
L1
L2
L3
L4
EF1
EF2
BL1
BL2
NL1
V1
V2
G1
G2
G3
S
S
S
S
S
CB1
D1 / D2
D3 / D4
F1
Electrical symbols
L1-L4 Recessed 6" LED / 4 total
L1-L2: wet-location listed for the shower.
V1-V2 Nola task lights / 2 total
BL1-BL2 Mirror surround / 2 total
NL1 Niche-top LED / 1 total / 3000K
66" above shower floor; light downward.
Complete wet-location assembly required.
EF1-EF2 Ceiling exhaust fans / 2 total
Duct each fan outdoors. EF2 sits over the toilet.
G1 Vanity GFCI / above counter
G2 Hair dryer GFCI / above counter
G3 Heated seat GFCI / confirm height
M1, M2: 24" x 32" each / GFCI fit TBD.
CB1 / Entry control bank
D1
L1 + L2
Shower dimmer
D2
L3 + L4
General dimmer
D3
V1 + V2
Vanity dimmer
D4
BL1 + BL2 + NL1
Ambient dimmer
F1
EF1 + EF2
Fan switch
Proposed centre locations
Device
X / from left
Y / from top
L1 / L2
28" / 84"
24"
L3 / L4
28" / 84"
84"
V1 / V2
112"
79 7/8" / 109 7/8"
BL1 / BL2
112"
79 7/8" / 109 7/8"
NL1
56"
-1 1/2"
EF1 / EF2
56" / 18"
60" / 109"
G1 / G2
112"
90" / 120"
G3
31"
124 7/8"
CB1
0"
92"
0
1'
2'
Actual size / 100%
* Bench support and drain cover removal / cleaning access: confirm before work.
Dashed lines: control groups, not cable routes. NL1 driver: accessible outside shower.
Electrician: approve complete LED assembly, dimmer and protection.
Ensuite bathroom
Proposed electrical / reflected ceiling plan
Sheet
E-01
Scale at letter size
3/8" = 1'-0" / 1:32
Date
05 Sep 2026
Preliminary / not for construction
Licensed Electrical Contractor review required